| To order call 804-798-7717 or E-mail us at sales@enviromation.org |
| To download calibration procedures for the AGTL TRANSMITER click here |
| FEATURES | APPLICATIONS
| Economical | Elevated Tanks
| Complete Package | Ground Level Tanks
| Field Proven | SCADA Systems
| Calibration Ready | Control Systems
| |
| Supply Voltage: 12 - 28 VDC | Zero and Span Adjustment Range:
| Rated Range: As specified | Span: 100% to 15% of rated range; 6.5 turndown ratio
| Temperature: Compensated: +25 to +150 degrees C | Zero suppression: 85% maximum w/ maximum turndown
| Operating: -40 to +176 degrees F | Enclosure: 10" x 8" x 4", NEMA 3R
|
| |
| ITEM | DESCRIPTION | PART NUMBER | QUANTITY
| A | ENCLOSURE 10"X8"X4",NEMA 3R | 004238001 | 1
| B | TERMINAL BLOCK, 3 SCREW TERMINALS | 019219003 | 1
| C | D/P TRANSMITTER | 015134001 | 1
| D1 | FITTING, MALE TO FEMALE ADAPTOR | 004135002 | 1
| D2 | FITTING, HEX NIPPLE | 004135003 | 1
| D3 | FITTING TEE | 004135001 | 1
| D4 | BLEED & TEST VALVE | 151135001 | 1
| D5 | SNUBBER | 041044003 | 1
| D6 | FITTING MALE CONNECTOR | 022110028 | 1
| D7 | TUBING, 1/4" COPPER | 004116001 | 1
| |
| AGTL-1 Tank Level Transmitter |
| The pressure transducer measures the pressure of water at the base of the water towers. The calibration range or span can be compressed from 100% to 15% of rated range: equivalent to a 6.5 turn down ratio. Zero can be suppressed from 0 to 85% of compression. Adjustment of the span and zero controls permits the calibrated range to be positioned anywhere within the calibrated range as shown below. |
|
![]()
|
© 2001 Enviromation | SureControl | Alarms |   SCADA System | Controls | Integrators | Solar | Visualization Software | Products
|